MW, MWh and MVA converter

MW measures power, the rate of flow; MWh measures energy, power over time: MWh = MW × hours. MVA is apparent power, and MW = MVA × power factor.

Convert
h

8,760 h in a year, 24 h in a day

Energy

876,000MWh

100 MW for 8,760 h

Method and data

Formula

E (MWh) = P (MW) × t (h)
P (MW) = S (MVA) × pf
Q (Mvar) = S × sin(acos pf)
S = sqrt(P^2 + Q^2)
I (A) = S (VA) / (sqrt(3) × V_LL)

Worked example

Energy from 100 MW at constant output
Power × timeEnergy
100 MW × 1 h100 MWh
100 MW × 24 h2,400 MWh
100 MW × 8,760 h876,000 MWh
100 MVA at three power factors
Power factorP (MW)Q (Mvar)Angle phi
0.8806036.9°
0.99043.5925.8°
0.959531.2218.2°

Assumptions

  • A year has 8,760 hours, or 8,784 in a leap year.
  • Power is constant over the period. For a varying output, the same formula holds with the average power.
  • The power triangle assumes sinusoidal voltage and current at one frequency; harmonics are ignored.
  • Q is shown as a positive magnitude. A lagging (inductive) load and a leading (capacitive) load with the same power factor have the same magnitude of Q.
  • Three-phase current assumes a balanced load and uses the line-to-line voltage; single-phase current uses the voltage across the load.

Definition: Power Factor

Guide: Electricity market units explained

On the Tera Intelligence map, each power plant, substation and line opens with its rated capacity and technical specifications, so a converted figure can be checked against the asset it describes. Explore the map

Questions

What is the difference between MW and MWh?
MW is a rate and MWh is an amount: a megawatt measures power at an instant, and a megawatt-hour is the energy delivered when one megawatt flows for one hour. A 100 MW plant at full output for one hour produces 100 MWh, and over a full year of 8,760 hours it would produce 876,000 MWh. Real plants produce less than that maximum, which is what the capacity factor measures.
How do I convert MVA to MW?
Multiply by the power factor: MW = MVA × pf. A 100 MVA load at a power factor of 0.9 draws 90 MW of active power, and the rest of the apparent power is reactive: Q = 100 × sin(acos 0.9) = 43.6 Mvar. Without a power factor the conversion cannot be made, because MVA includes reactive power that does no useful work.
What power factor should I assume?
Use the figure from the equipment data sheet, the connection agreement or the grid code, not a rule of thumb. Many grid codes ask generators to be able to operate anywhere between 0.95 leading and 0.95 lagging; in the United States, FERC Order 827 (June 2016) set that range for new wind and solar plants. Synchronous generator nameplates commonly state a rated power factor of 0.8 to 0.9. The 0.9 used on this page is a default for the worked result, not a recommendation.
How many homes does 1 MW power?
It depends on how much electricity a household uses and on the plant's capacity factor, so no single figure is right. Homes = (P × 8,760 h × CF) / annual consumption per household. Hypothetical example, not an average: a 1 MW plant with a capacity factor of 25% produces 1 × 8,760 × 0.25 = 2,190 MWh a year; if each home used 5 MWh a year, that would equal the yearly use of 438 homes. Household consumption differs several-fold between countries, so use the local figure, and note that matching yearly energy is not the same as supplying those homes at every hour.
How do I convert MVA to amps?
For a three-phase circuit, divide the apparent power by the square root of 3 times the line-to-line voltage: I = S / (sqrt(3) × V_LL), with S in VA and V in volts. 100 MVA at 132 kV gives 100,000,000 / (1.732 × 132,000) = 437 A. For a single-phase circuit, I = S / V. Current follows MVA, not MW, so a lower power factor means more current for the same active power.